====== Victron & Pytes ====== ===== 1. Product & System compatibility ===== === 1.1 A GX device is required, eg Cerbo GX, etc === It is essential to use the BMS-Can (500 kbit/s) connection type of a [[venus-os:start|GX device]] with these batteries for communication of charge and discharge limits, error codes and state of charge. It is possible to use either the BMS-Can or VE.Can ports with this battery. Depending which one you use will require additional configuration on the batteries side, please see the documentation linked below for instructions. The minimum supported GX firmware version is v3.31. It is recommended to use the latest firmware version on new installations and when trouble shooting issues. The minimum supported Pytes firmware version is 1.10.18. This is displayed at v18.1 on the GX device and VRM. Connecting a Pytes battery to the GX device will require enabling DVCC, and disabling SVS and STS. {{:battery_compatibility:cleanshot_2024-06-18_at_22.34.12.jpg?400|}} {{:battery_compatibility:cleanshot_2024-06-18_at_22.32.25.jpg?400|}} {{:battery_compatibility:cleanshot_2024-06-18_at_22.32.32.jpg?400|}} {{:battery_compatibility:cleanshot_2024-06-18_at_22.32.40.jpg?400|}} {{:battery_compatibility:cleanshot_2024-06-18_at_22.36.44.jpg?400|}} {{:battery_compatibility:cleanshot_2024-06-18_at_22.36.55.jpg?400|}} === 1.2 All 48V Multis, MultiPlus, Quattros and RS models are compatible === The minimum supported firmware version for VE.Bus models is 469. Minimum supported firmware for RS models is 1.16. Updating to the latest firmware is recommended for new installations, and troubleshooting issues. These VE.Bus inverter/charger units must be connected to the [[venus-os:start|GX device]] via the VE.Bus connection port. In grid connected systems, advanced control functions are configurable in the ESS settings on the [[venus-os:start|GX device]]. In off-grid systems, the control functions of the Battery Management System (BMS) are built into the latest version of the [[venus-os:start|GX device]]. === 1.3 Solar Charger compatibility === All 48V BlueSolar and SmartSolar MPPT Chargers are compatible. Some of our Solar Chargers feature a VE.Direct communication port, some feature a VE.Can communication port, and some feature both. Both of these types of communication ports can be used to connect the Solar charger to the GX Device. Such connection is mandatory, because it is used to regulate charge currents and voltages. ===== 2. Minimum battery sizing ===== For reliable operation there are minimum numbers of batteries required for different Victron inverters. Please contact your battery supplier for these specifications. ===== 3. Further system integration documentation ===== {{ :battery_compatibility:ebox_series.pdf |Installation and configuration manual with Victron Energy}} {{ :battery_compatibility:pytes.pdf |Pytes Victron Guide}} {{ :battery_compatibility:victron-configure3-setting-with-pytes.pdf | Victron VE.Configure3 settings with Pytes}} {{ :battery_compatibility:pytes_ebox_manual.pdf | Ebox Series manual}} Further details about installation and configuration is available from your battery manufacturer. Improvements CVL (Charge Voltage Limit) regulation were added to Pytes firmware versions 1.10.18. Earlier versions will still connect but are not supported, and may charge/discharge cycle when at 100% state of charge. ===== 4. Support ===== Support for this battery should first come from your battery supplier. Pytes has a service email at ess_support@pytesgroup.com Support from Victron is limited our online [[https://community.victronenergy.com/index.html|Victron Community]] page.