====== Victron & BSLBATT Lithium batteries ====== | ====== Victron & BSLBATT Lithium batteries ====== | ||
- | Introduction | + | [[https:// |
- | WISDOM INDUSTRIAL POWER Co.,LTD (www.lithium-battery-factory.com) produces BSLBATT LiFePO4 batteries for 12V, 24V and 48V systems for Solar and Motive system, already had over 18 years. | + | =====1. Product & System compatibility ===== |
- | + | ||
- | ===== Product & System compatibility ===== | + | |
The integration with Victron and BSLBATT batteries has been tested, complies with Victron' | The integration with Victron and BSLBATT batteries has been tested, complies with Victron' | ||
- | === Offgrid, Backup and Energy Storage Systems (ESS) === | + | ===1.1 Offgrid, Backup and Energy Storage Systems (ESS) === |
Victron + BSLBATT can be used for the following system types: | Victron + BSLBATT can be used for the following system types: | ||
Line 18: | Line 17: | ||
__Special note for Off-Grid systems__ | __Special note for Off-Grid systems__ | ||
- | For Off-grid systems, its strongly recommend to make sure there is a minimum of DC-Coupled PV (= MPPT Solar Charger) in the system. Ie. not only AC-Coupled PV. Also, minimum battery configuration, | + | For Off-grid systems, its strongly recommend to make sure there is a minimum of a single |
- | === A GX device is required, eg Cerbo GX, etc === | + | === 1.2 A GX device is required, eg Cerbo GX, etc === |
- | It is essential to use the BMS-Can (or CAN-bus) connection of a [[venus-os: | + | It is essential to use the BMS-Can (or CAN-bus) connection of a [[venus-os: |
The minimum supported firmware version for the [[venus-os: | The minimum supported firmware version for the [[venus-os: | ||
- | === All 48V Multis, MultiPlusses, | + | === 1.3 All 48V Multis, MultiPlusses, |
The minimum supported firmware version is 469. Updating to the latest firmware is recommended for new installations, | The minimum supported firmware version is 469. Updating to the latest firmware is recommended for new installations, | ||
Line 37: | Line 36: | ||
- | === Solar Charger compatibility === | + | === 1.4 Solar Charger compatibility === |
All 48V BlueSolar and SmartSolar VE.Direct MPPT Chargers are compatible (*). | All 48V BlueSolar and SmartSolar VE.Direct MPPT Chargers are compatible (*). | ||
Line 46: | Line 45: | ||
(*) with exception of the models “BlueSolar MPPT 150/70 CAN-bus” and “BlueSolar MPPT 150/85 CAN-bus” which are end-of-life since 2019. Legacy systems, historically installed with this configuration using the allow to charge contacts may be possible, speak to your dealer for more information. | (*) with exception of the models “BlueSolar MPPT 150/70 CAN-bus” and “BlueSolar MPPT 150/85 CAN-bus” which are end-of-life since 2019. Legacy systems, historically installed with this configuration using the allow to charge contacts may be possible, speak to your dealer for more information. | ||
+ | |||
+ | It should be noted that one should always connect the battery before connecting the solar input to any MPPT. | ||
+ | |||
+ | The CAN-bus baud rate is 500kbis/s for communication between BSL batteries and any GX device. | ||
=== Battery compatibility === | === Battery compatibility === | ||
- | The following | + | All BSL batteries are supported |
- | ^ BSLBATT type ^ | + | |
- | | B-LFP48-100E | + | |
- | | B-LFP48-120E | + | |
- | | B-LFP48-200PW | + | |
- | ===== Configuration settings ===== | + | |
+ | ===== 2. Minimum Battery Sizing ===== | ||
+ | |||
+ | The following information is provided by BSL, it is reproduced here for your convenience and should always be confirmed with the latest BSL manuals and specifications. | ||
+ | |||
+ | It should also be noted that these are the minimum requirements for the BSL battery range and that each unit can be paralleled many times over. Please consult the relevant manual on how many units can be placed in parallel. | ||
+ | |||
+ | The table below shows the __**minimum**__ number of battery modules required for the specified inverter/ | ||
+ | |||
+ | === Battery Modules Required - 5.1kWh/ | ||
+ | |||
+ | |Phases| | ||
+ | | Inverter/ | ||
+ | | Multiplus & Multiplus II & MP-II GX 48/ | ||
+ | | Multiplus & Multiplus II & MP-II GX 48/ | ||
+ | | Inverter RS & Multi RS 48/ | ||
+ | | Quattro 48/ | ||
+ | | Quattro 48/ | ||
+ | | Quattro 48/ | ||
+ | | Quattro 48/ | ||
+ | | EasySolar & EasySolar-II 48/ | ||
+ | | EasySolar 48/ | ||
+ | |||
+ | === Battery Modules Required - 6.4kWh/ | ||
+ | |||
+ | |Phases| | ||
+ | | Inverter/ | ||
+ | | Multiplus & Multiplus II & MP-II GX 48/ | ||
+ | | Multiplus & Multiplus II & MP-II GX 48/ | ||
+ | | Inverter RS & Multi RS 48/ | ||
+ | | Quattro 48/ | ||
+ | | Quattro 48/ | ||
+ | | Quattro 48/ | ||
+ | | Quattro 48/ | ||
+ | | EasySolar & EasySolar-II 48/ | ||
+ | | EasySolar 48/ | ||
+ | |||
+ | === Battery Modules Required - 8.2kWh/ | ||
+ | |||
+ | |Phases| | ||
+ | | Inverter/ | ||
+ | | Multiplus & Multiplus II & MP-II GX 48/ | ||
+ | | Multiplus & Multiplus II & MP-II GX 48/ | ||
+ | | Inverter RS & Multi RS 48/ | ||
+ | | Quattro 48/ | ||
+ | | Quattro 48/ | ||
+ | | Quattro 48/ | ||
+ | | Quattro 48/ | ||
+ | | EasySolar & EasySolar-II 48/ | ||
+ | | EasySolar 48/ | ||
+ | |||
+ | === Battery Modules Required - 10.2kWh/ | ||
+ | |||
+ | |Phases| | ||
+ | | Inverter/ | ||
+ | | Multiplus & Multiplus II & MP-II GX 48/ | ||
+ | | Multiplus & Multiplus II & MP-II GX 48/ | ||
+ | | Inverter RS & Multi RS 48/ | ||
+ | | Quattro 48/ | ||
+ | | Quattro 48/ | ||
+ | | Quattro 48/ | ||
+ | | Quattro 48/ | ||
+ | | EasySolar & EasySolar-II 48/ | ||
+ | | EasySolar 48/ | ||
+ | |||
+ | ===== 3. CAN-Bus wiring between battery and GX device ===== | ||
+ | |||
+ | In order to connect your battery to the relevant GX device, one must utilize a "Type B" cable, the Victron part number for this cable is : ASS030720018. | ||
+ | |||
+ | One should always terminate the CAN port on the GX device when it comes to installing BSL batteries. | ||
+ | |||
+ | ===== 4. Configuration settings ===== | ||
+ | |||
+ | === 4.1 Charger tab === | ||
+ | |||
+ | ^ VEConfigure Charge Parameter | ||
+ | | Battery type | Lithium | | ||
+ | | Charge curve | Fixed | | ||
+ | | Absorption voltage | ||
+ | | Float voltage (1) | 54.8 V | | ||
+ | | Absorption time | 1 Hr | | ||
+ | |||
+ | === 4.2 Inverter Settings === | ||
+ | |||
+ | In the Inverter tab of VEConfigure | ||
+ | ^VEConfigure Inverter Parameter | ||
+ | |DC input low shut-down | 48V | | ||
+ | |DC input low restart | ||
+ | |DC input low pre-alarm* | 51V | | ||
+ | |||
+ | === 4.3 ESS Settings === | ||
+ | |||
+ | ^ ESS Parameter ^ Settings ^ | ||
+ | |Sustain voltage. | ||
+ | |Dynamic cut-off values | Set all values to 47V | | ||
+ | |Restart offset: | ||
+ | |Voltage to restart PV: | 53.5V | | ||
+ | |||
+ | === 4.4 All Settings | ||
Integration instructions for Victron and BSLBATT is described in this manual - | Integration instructions for Victron and BSLBATT is described in this manual - | ||
- | {{ : | + | {{ : |
+ | |||
+ | === 4.5 Specific manuals for various models of battery: === | ||
+ | |||
+ | * 5.1kWh battery- {{ : | ||
+ | * 6.4kWh battery- {{ : | ||
+ | * 7kWh battery- {{ : | ||
+ | * 8.2kWh battery- {{ : | ||
+ | * 10.2kWh battery- {{ : | ||
+ | * 15kWh battery- {{ : | ||
+ | * Powerline-5 battery- {{ : | ||
+ | |||
+ | ===== 5. Solar Charging ===== | ||
+ | |||
+ | ==== 5.1 Victron MPPT charger settings ==== | ||
+ | |||
+ | Victron MPPT charge characteristics are automatically configured & governed by the [[venus-os: | ||
+ | |||
+ | Select Battery > Preset > Smart Lithium | ||
+ | |||
+ | ^ MPPT Parameter ^ Setting ^ | ||
+ | |Battery voltage | ||
+ | |Absorption voltage | ||
+ | |Float voltage | ||
+ | |||
+ | The MPPT should also be configured correctly in case of the GX device failing and thus not being able to throttle up or down the charging currents and voltages. | ||
+ | |||
+ | ===== 6. Battery configured correctly ===== | ||
Here is a series of screenshots showing the result: | Here is a series of screenshots showing the result: | ||
Line 67: | Line 191: | ||
{{: | {{: | ||
+ | |||
+ | ===== 7. Trouble shooting ===== | ||
+ | |||
+ | ==== 7.1 Battery not turning on ==== | ||
+ | |||
+ | If the battery does not want to turn on, there may be a variety of reasons for this including lightning strikes or surging which may have taken place. If this is the case, one should contact their installer to remove the battery. The battery will then be take to the distributer and will then and only then be opened and inspected. | ||
+ | |||
+ | ==== 7.2 Battery has a flashing red light ==== | ||
+ | |||
+ | The battery may have an error, be it internal or externally caused. One should hold in the reset button for 5 seconds, turning the battery off and then hold in the reset button for another 5 seconds once the battery has been off for longer than 10 seconds. This will reset the battery and clear the error. If the error does not clear, one should contact their installer to remove the battery. The battery will then be take to the distributer and will then and only then be opened and inspected. | ||
+ | |||
+ | ==== 7.3 Battery has no voltage or 16V on the battery terminals ==== | ||
+ | |||
+ | The battery may have have a faulty breaker or the battery may have been subjected to a surge or lightning strike. If your inverter is reading a low battery reading, one should contact their installer to remove the battery. The battery will then be take to the distributer and will then and only then be opened and inspected. | ||
+ | |||
+ | ===== 8. Warranty documentation | ||
+ | |||
+ | All BSL batteries are subject to warranty specific documentation which can be found here: {{: | ||
+ | |||
+ | ===== 9. Battery Installed correctly ===== | ||
{{: | {{: | ||
+ | |||
{{: | {{: | ||
Line 74: | Line 219: | ||
===== Further Information ===== | ===== Further Information ===== | ||
+ | |||
+ | For more product information, | ||
For information about where to buy or find suitably qualified installers, visit the [[https:// | For information about where to buy or find suitably qualified installers, visit the [[https:// |
battery_compatibility/bsl.1618475280.txt.gz · Last modified: 2021-04-15 10:28 by bslbatt