Line 154: Line 154:
 If you are using firmware v1.08 or newer this error indicates that the internal dc voltage is too high. This error will auto-reset. If the error does not auto-reset disconnect the charge controller from all power-sources, wait 3 minutes, and power up again. If the error persists the charge controller is probably faulty. If you are using firmware v1.08 or newer this error indicates that the internal dc voltage is too high. This error will auto-reset. If the error does not auto-reset disconnect the charge controller from all power-sources, wait 3 minutes, and power up again. If the error persists the charge controller is probably faulty.
  
-==== Err 38, Err 39 - PV Input shutdown ====+==== Err 38, Err 39 and Err 80 to Err 87 - PV Input shutdown ====
  
-When these error show, the PV Input is internally shorted in order to protect the battery from over-charging the battery.+When these errors show, the PV Input is internally shorted in order to protect the battery from over-charging.
  
 Prior to any other trouble shooting, make sure to update to the latest firmware version. Prior to any other trouble shooting, make sure to update to the latest firmware version.
Line 162: Line 162:
 Possible reasons for this error to occur: Possible reasons for this error to occur:
  * The Battery voltage (12/24/36/48V) is set incorrectly. Use VictronConnect to set the right Battery Voltage.  * The Battery voltage (12/24/36/48V) is set incorrectly. Use VictronConnect to set the right Battery Voltage.
- * There is another charger connected to the battery, which chargers at a higher voltage. The solution is to make sure that charge voltages configured in the MPPT match the other chargers in the system. In case equalisation is set in one of the other chargers, especially at higher voltages such as 16 or 17Vthen configure the same in the MPPT. Even when the MPPT is not used for equalisation. + * There is another device connected to the battery, which is configured to a higher voltage. For example a MultiPlus, configured to equalise at 17 Voltswhile in the MPPT this is not configured
- * The battery is disconnected using a manual switch, without first disconnecting the PV array. Which is not ideal but otherwise harmless. If necessary the voltage trip-level for the PV Short protection can be increased by raising the Equalization voltage set-point; which works even when Equalization itself is not enabled . +
- * The battery is disconnected using a Lithium charge relay connected to the “allow-to-charge” output of a BMS. Consider wiring this signal to the Remote terminal of the charger instead. This shuts down the charger gracefully+
 Error recovery: Error recovery:
- * Error 38: First disconnect the solar panels and disconnect the battery. Wait for 3 minutes, then reconnect the battery first and next the panels. + * Error 38 and Errors 84 to 87: First disconnect the solar panels and disconnect the battery. Wait for 3 minutes, then reconnect the battery first and next the panels. 
- * Error 39: The charger will automatically resume operation once the battery voltage drops below its maximum voltage setting (normally Equalisation or Absorption voltages), for 250V versions or float voltage for the other units. It can also takes a minute to reset the fault.+ * Error 39: The charger will automatically resume operation once the battery voltage drops below its maximum voltage setting (normally Equalisation or Absorption voltages). It can also takes a minute to reset the fault
 + * Errors 80 to 83: First disconnect the solar panels and disconnect the battery, then follow the reset procedure described [[mppt_pv_short_relay_reset|here]]
  
 If the error persists the charge controller is probably faulty. If the error persists the charge controller is probably faulty.
Line 219: Line 218:
 Re-charge the battery or reduce the AC loads to continue operation. Re-charge the battery or reduce the AC loads to continue operation.
  
-If the error immediately pops up when switching on the inverter (without load) on a full battery the cause is most likely a broken internal fuse.+If the error immediately pops up when switching on the inverter (without load) on a full battery the cause is most likely a broken replaceable internal fuse. Contact your Victron dealer for support
 ==== Err 55, Err 56, Err 58 - Inverter self test failed ==== ==== Err 55, Err 56, Err 58 - Inverter self test failed ====
 The inverter performs diagnostic tests before it activates its output. In the case that one of these tests fails an error message is displayed and the inverter does not turn on. The inverter performs diagnostic tests before it activates its output. In the case that one of these tests fails an error message is displayed and the inverter does not turn on.
Line 230: Line 229:
 This error will not auto-reset. Check the installation and restart the unit using the power-switch. This error will not auto-reset. Check the installation and restart the unit using the power-switch.
  
 +==== Err 59 - ACIN1 relay test fault ====
 +
 +Automatic checking of the disconnect means failure.
 +This usually indicates a broken relay (sticky contact) in the AC input stage.
  
 ==== Information 65 - Communication warning ==== ==== Information 65 - Communication warning ====
Line 237: Line 240:
 The controller is being paralleled to another controller that has different settings and/or a different charge algorithm. The controller is being paralleled to another controller that has different settings and/or a different charge algorithm.
  
-Make sure all settings are the same and update firmware on all  chargers to the latest version+Make sure all settings are the same and update firmware on all chargers to the latest version.
  
  
 ==== Err 67 - BMS Connection lost ==== ==== Err 67 - BMS Connection lost ====
-The charger is configured to be controlled by a BMS, but it does not receive any control messages from a BMSThe charger stopped charging by reducing the output voltage to the battery base voltage (12V/24V/36V/48V), as a safety precaution.+ 
 +This error shows when the charger is configured to be controlled by a BMS, but does not receive any BMS control messages. In that situation, the charger stops charging by reducing its output voltage to the battery base voltage (12V/24V/36V/48V). This is a safety mechanism, the reason to still enable the output is to allow a system to self-recover from a battery low situation.
  
 Solar Chargers only show this error when there is solar power available and thus the device is ready to initiate charging. It does not show at night. And in case there is a permanent problem, the error will raise in the morning and clear at night, and so forth. Solar Chargers only show this error when there is solar power available and thus the device is ready to initiate charging. It does not show at night. And in case there is a permanent problem, the error will raise in the morning and clear at night, and so forth.
  
-Check the connection between the charger and the BMS.+Solution: check the connection between the charger and the BMS.
  
 __How to reconfigure the charger to standalone mode__ __How to reconfigure the charger to standalone mode__
Line 251: Line 255:
 Our Chargers and Solar Chargers automatically configure themselves to be BMS-controlled when they are connected to one; either direct or via a GX Device. And that setting is semi-permanent: power cycling the charger will not reset it. Our Chargers and Solar Chargers automatically configure themselves to be BMS-controlled when they are connected to one; either direct or via a GX Device. And that setting is semi-permanent: power cycling the charger will not reset it.
  
-Here is what needs to be done to make the charger operate in stand-alone mode againi.e. not controlled by a BMS:+When removing charger from such systemand reusing it in system without BMS, that setting needs to be cleared.  
 +Here is how to do that:
  
   * Chargers with LCD display: go into the setup menu, and change setting ‘BMS’ from ‘Y’ to ‘N’ (setup item 31).   * Chargers with LCD display: go into the setup menu, and change setting ‘BMS’ from ‘Y’ to ‘N’ (setup item 31).
Line 275: Line 280:
  
 This error indicates an issue in the configuration. There are units present on the same can bus that have different system configurations. This error indicates an issue in the configuration. There are units present on the same can bus that have different system configurations.
-Please ensure that all units are set to either "Single Phase" or "Three Phase"+Please ensure that all units are set to either "Single Phase" or "Three Phase" and all units are set to either "50Hz" or "60Hz".
 All units will remain off until the configuration is fixed, after which the units will resume operation. All units will remain off until the configuration is fixed, after which the units will resume operation.
  
Line 281: Line 286:
 Applies to Inverter RS models. Firmware versions 1.11 and higher. Applies to Inverter RS models. Firmware versions 1.11 and higher.
  
-The Inverter RS model used cannot be paired with a Multi RS and/or Transfer Switch+Inverter RS units cannot be paired with a Multi RS and/or Transfer Switch.
-Only Inverter RS models with a production code newer than HQYYWW can be used for this purpose. +
-Only the incompatible Inverter RS units will remain off.+
  
 ==== Err 71 - Network misconfigured ==== ==== Err 71 - Network misconfigured ====
Line 291: Line 294:
 All units will remain off until the until the firmwares are updated, after which the units will resume operation. All units will remain off until the until the firmwares are updated, after which the units will resume operation.
  
-==== Err 80 to Err 87 PV Input shutdown ====+==== Err 72 Phase rotation ==== 
 +Applies to Inverter RS and Multi RS models. Firmware versions 1.12 and higher.
  
-When these error show, the PV Input is internally shorted in order to protect the battery from over-charging the battery.+Check the if the phase order is correct L1->L2->L3.
  
-Prior to any other trouble shootingmake sure to update to the latest firmware version.+The inverters remain operationalthey won't connect to the grid. Once the issue is resolved the units will connect.
  
-Possible reasons for this error to occur: +==== Err 73 - Multiple AC inputs ==== 
- * The Battery voltage (12/24/36/48V) is set incorrectly. Use VictronConnect to set the right Battery Voltage. +Applies to Inverter RS and Multi RS modelsFirmware versions 1.12 and higher.
- * There is another charger connected to the battery, which chargers at a higher voltageThe solution is to make sure that charge voltages configured in the MPPT match the other chargers in the system. In case equalisation is set in one of the other chargers, especially at higher voltages such as 16 or 17V, then configure the same in the MPPT. Even when the MPPT is not used for equalisation. +
- * The battery is disconnected using a manual switch, without first disconnecting the PV array. Which is not ideal but otherwise harmless. If necessary the voltage trip-level for the PV Short protection can be increased by raising the Equalization voltage set-point; which works even when Equalization itself is not enabled . +
- * The battery is disconnected using a Lithium charge relay connected to the “allow-to-charge” output of a BMS. Consider wiring this signal to the Remote terminal of the charger instead. This shuts down the charger gracefully.+
  
-Error recovery: +Per phase only one active connection to the grid is allowedremove or switch off the redundant connection.
- * Errors 80 to 83: First disconnect the solar panels and disconnect the batterythen follow the reset procedure described [[mppt_pv_short_relay_reset|here]]. +
- * Errors 84 to 87: First disconnect the solar panels and disconnect the battery. Wait for 1 minute, then reconnect the battery first and next the panels.+
  
-If the error persists the charge controller is probably faulty.+The inverters remain operational, they won't connect to the grid. Once the issue is resolved the units will connect. 
 + 
 +==== Err 74 - Phase overload ==== 
 +Applies to Inverter RS and Multi RS models. Firmware versions 1.12 and higher. 
 + 
 +The number of inverters in parallel doesn't match with the transfer capabilities of the ac input relay of the Multi RS or Transfer switch. 
 +Firmware v1.12 does not support parallel units and a grid connection, so any combination of a Multi RS with a grid connection with more than one unit in parallel will trigger this error code on the Multi RS. The Multi RS only supports 3 units in 3-phase configuration at the moment. 
 + 
 +The inverters remain operational, they won't connect to the grid. Once the issue is resolved the units will connect. 
 + 
 +==== Err 80, Err 81, Err 82, Err 83, Err 84, Err 85, Err 86 and Err 87 - PV Input shutdown ==== 
 +Refer to [[mppt-error-codes#err_38_err_39_and_err_80_to_err_87_-_pv_input_shutdown|Error 38]] description.
  
 ==== Err 114 - CPU temperature too high ==== ==== Err 114 - CPU temperature too high ====
Line 327: Line 337:
 To fix this the update needs to be retried, download the correct firmware for your device from the [[https://professional.victronenergy.com/|Victron Professional Portal]] To fix this the update needs to be retried, download the correct firmware for your device from the [[https://professional.victronenergy.com/|Victron Professional Portal]]
  
-When your Venus GX device is connected to VRM, you can do a remote firmware update using this firmware file. You can do this via the VRM website or using the VRM tab in VictronConnect. VictronConnect can also be used together with the firmware file to update using a Bluetooth connection.+When your GX device is connected to VRM, you can do a remote firmware update using this firmware file. You can do this via the VRM website or using the VRM tab in VictronConnect. VictronConnect can also be used together with the firmware file to update using a Bluetooth connection.
  
 The procedure to add the file to VictronConnect and start the update is described here: [[https://www.victronenergy.com/media/pg/VictronConnect_Manual/en/firmware-updates.html#UUID-705fe0d3-30d8-e6e6-aad1-856f4ac6e3b3|9. Firmware updates]]  The procedure to add the file to VictronConnect and start the update is described here: [[https://www.victronenergy.com/media/pg/VictronConnect_Manual/en/firmware-updates.html#UUID-705fe0d3-30d8-e6e6-aad1-856f4ac6e3b3|9. Firmware updates]] 
Line 353: Line 363:
  
 ==== Err 201 - Internal DC voltage error ==== ==== Err 201 - Internal DC voltage error ====
-Applies to the MPPT RS, Inverter RS and Multi RS+Applies to the MPPT RS, Inverter RS and Multi RS.
  
-Internal DC voltage measurement error, is raised in case an internal (high-) voltage measurement does not match certain criteria. And it means that a measurement circuit inside the unit is broken.+This “Internal DC voltage measurement error, is raised in case an internal (high-) voltage measurement does not match certain criteria. 
  
-Make sure to update the firmware to at least v1.08, in previous firmwares the limits were too strict. And it could trigger falsely during MPPT start-up in the morning and MPPT shutdown in the evening.+First, make sure to update the firmware to v1.08 or later. The limits were too strict in earlier versions. And it could trigger falsely during MPPT start-up in the morning and MPPT shutdown in the evening.
  
-The unit might have seemingly worked fine before the firmware update; but it is really brokennot safe for use, and if it hadn't stopped working already then it would have stopped working soon. Which is why we added this internal check.+If the error still occurs after updating to v1.08 or later, then it means that a measurement circuit inside the unit is broken.
  
-This error will not auto-reset. Check the installation and restart the unit using the power-switch. If the error persists the unit is probably faulty and must be sent in for repair/replacement.+This error will not auto-reset. Check the installation and restart the unit using the power-switch. If the error persists, even after above mentioned firmware update, the unit is most likely faulty and must be sent in for repair/replacement.
  
 ==== Err 202 - Internal GFCI sensor error ==== ==== Err 202 - Internal GFCI sensor error ====