 Follow below procedure only if (a) the charger is not measuring any PV voltage when it should (i.e. during the day, with sun shinning, and all connections are ok). (b) the charger no longer charges the battery and measuring the PV Input with a MultiMeter in resistance mode shows a few Ohms or lower. (c ) the charger no longer charges an error 80 to 87 is/was shown. Follow below procedure only if (a) the charger is not measuring any PV voltage when it should (i.e. during the day, with sun shinning, and all connections are ok). (b) the charger no longer charges the battery and measuring the PV Input with a MultiMeter in resistance mode shows a few Ohms or lower. (c ) the charger no longer charges an error 80 to 87 is/was shown.
-==== Reset latching relay ====+==== Reset procedure ====
 To recover from such failure, the below reset procedure must be followed.  To recover from such failure, the below reset procedure must be followed. 
   - Disconnect the PV Input terminals.   - Disconnect the PV Input terminals.