multiplus_faq
Differences
This shows you the differences between two versions of the page.
Both sides previous revisionPrevious revisionNext revision | Previous revision | ||
multiplus_faq [2019-10-17 13:48] – [3.1 Derating of the power factor] guystewart | multiplus_faq [2024-07-17 06:57] (current) – [4.1 PowerAssist] guy_stewart | ||
---|---|---|---|
Line 10: | Line 10: | ||
- | Some generators are more suitable than others for use with inverter/ | + | Some generators are more suitable than others for use with inverter/ |
For example; some things to look for when selecting a generator is a high quality alternator and AVR (auto voltage regulation). | For example; some things to look for when selecting a generator is a high quality alternator and AVR (auto voltage regulation). | ||
Line 35: | Line 35: | ||
If your generator is smaller than the recommended size for your inverter/ | If your generator is smaller than the recommended size for your inverter/ | ||
+ | If you do want an inverter based generator (eg for noise reasons under lower loading), get one that is at least 30% larger than required than an equivalent AVR based model to help prevent nuisance overloads. | ||
+ | |||
+ | It is also important to look at the DUTY CYCLE rating of the generator. Some generators are marketed for their peak output, but may only be designed to sustain 50% of that peak load rating for longer periods of time. | ||
+ | |||
+ | Battery charging is a very heavy use case load for a generator, so make sure it is up to the job, and the installation has plenty of good airflow and ventilation when operating to allow for heat to dissipate. | ||
+ | |||
+ | Some generators are only designed to operate for several hours, before requiring time to rest and cool down. Make sure this limitation is part of your load profile and system design. | ||
==== Operation ==== | ==== Operation ==== | ||
Line 45: | Line 52: | ||
- | ==== Software | + | ==== Software |
The settings which you should attempt first are ' | The settings which you should attempt first are ' | ||
- | If the generator will still not synchronise or disconnects, | + | If the generator will still not synchronise or disconnects, |
Lastly, adjusting the settings for Voltage and Frequency windows. These are higher risk to your appliances, they should only be used cautiously when it is confirmed that the loads will tolerate the out of specification power supply. This should be done by a competent technician with the aid of a multimeter and only opened so far as to allow for safe functionality. | Lastly, adjusting the settings for Voltage and Frequency windows. These are higher risk to your appliances, they should only be used cautiously when it is confirmed that the loads will tolerate the out of specification power supply. This should be done by a competent technician with the aid of a multimeter and only opened so far as to allow for safe functionality. | ||
Line 59: | Line 66: | ||
Warning: changing these settings will allow to feed-through current that may be of insufficient quality for the electrical requirements of your equipment. | Warning: changing these settings will allow to feed-through current that may be of insufficient quality for the electrical requirements of your equipment. | ||
- | For information on VE-Configure | + | For information on VEConfigure |
- | ====== 1. In the “Grid” tab of VE-Configure: ====== | + | ====== 1. In the “Grid” tab of VEConfigure: ====== |
| | ||
Line 102: | Line 109: | ||
- | ===== 1.5 Loss of mains detection (LOM) ===== | + | ===== 1.5 Loss of mains detection (LOM) (Only applicable to ESS systems) ===== |
+ | |||
+ | This part is only applicable on systems where a grid-code is selected (generally only ESS systems) on an off-grid system a grid code should not be used and in the selection box for grid code, ' | ||
Loss of mains detection will push and pull at voltage and frequency to see if there is still a generating source. This process can cause issues with some generators, or high impedance connections to generators. | Loss of mains detection will push and pull at voltage and frequency to see if there is still a generating source. This process can cause issues with some generators, or high impedance connections to generators. | ||
Line 126: | Line 135: | ||
- | ====== 2. In the “General” tab of VE-Configure: ====== | + | ====== 2. In the “General” tab of VEConfigure: ====== |
{{:: | {{:: | ||
Line 141: | Line 150: | ||
===== 2.2 AC Input Current Limit ===== | ===== 2.2 AC Input Current Limit ===== | ||
- | The charger on the Multiplus is very powerful. If you have an existing generator that is not able to supply the maximum charging current of the Multi, you will need to adjust the AC Input Current Limit in the General Tab of VE-Configure. | + | The charger on the Multiplus is very powerful. If you have an existing generator that is not able to supply the maximum charging current of the Multi, you will need to adjust the AC Input Current Limit in the General Tab of VEConfigure. |
A reasonable starting point for the AC Current input limit is 80% of the generator capacity in Watts. For example: | A reasonable starting point for the AC Current input limit is 80% of the generator capacity in Watts. For example: | ||
Line 162: | Line 171: | ||
- | ====== 3. In the " | + | ====== 3. In the " |
{{: | {{: | ||
Line 174: | Line 183: | ||
This leading or lagging power factor will have the effect of demanding more kVa from the generator for the same or less DC Watts delivered to the batteries. You may need to further reduce the DC Current Limit in the Charger tab of VEConfigure if the generator continues to overload after changing this setting. | This leading or lagging power factor will have the effect of demanding more kVa from the generator for the same or less DC Watts delivered to the batteries. You may need to further reduce the DC Current Limit in the Charger tab of VEConfigure if the generator continues to overload after changing this setting. | ||
- | Effectively, | + | Effectively, when Weak AC is enabled, the total charge current possible will be less that the rated maximum charge current output of the charger (under normal conditions). |
**Important note:** | **Important note:** | ||
- | A detailed description of all settings is available in the VE-Configure | + | A detailed description of all settings is available in the VEConfigure |
- | ====== 4. In the “Inverter” tab of VE-Configure: ====== | + | ====== 4. In the “Inverter” tab of VEConfigure: ====== |
===== 4.1 PowerAssist ===== | ===== 4.1 PowerAssist ===== | ||
+ | |||
+ | {{:: | ||
The [[https:// | The [[https:// | ||
Line 189: | Line 200: | ||
If you have a small generator and have trouble getting connected or staying connected, Disable PowerAssist to allow the device to reduce the AC input current limit. | If you have a small generator and have trouble getting connected or staying connected, Disable PowerAssist to allow the device to reduce the AC input current limit. | ||
+ | There is an additional configurable parameter of PowerAssist called "Boost factor" | ||
+ | When the Multi is charging from the generator, and the current required exceeds the AC input current limit (due to a sudden additional load) then the Multi will switch to PowerAssist mode. | ||
+ | |||
+ | At that moment the precise current needed is unknown. The Multi uses the " | ||
+ | |||
+ | In some cases this multiple is either too high, or too low. This would most likely present as the generator unable to stay connected, or fluctuations to the frequency and voltage. | ||
+ | |||
+ | The fastest way to diagnose if setting may be interfering with your specific generator and load operation is to disable power assist entirely. If that resolves the issue, then try reducing the Assist current boost factor down until it works reliably and still getting the benefit of the feature without the interference. The optimal value for this will depend on the size of the inverter, the size of the generator, and the size of the load. | ||
+ | |||
+ | ====== 5. Generator control in 3 phase and parallel systems ====== | ||
+ | |||
+ | There is some specific and non-intuitive conditions when setting AC input current limits, and Charge Current limits for Large systems that involve more than one MultiPlus, and/or a GX device. | ||
+ | |||
+ | Those specific details are articulated here: | ||
+ | https:// | ||
+ | |||
+ | Described in the online training theory here: | ||
+ | @ 38 minutes and 43 seconds - https:// | ||
+ | |||
+ | Demonstrated in the 3 phase installation training here: | ||
+ | @ 25 minutes - https:// | ||
====== Still not connecting? ====== | ====== Still not connecting? ====== | ||
- | If the unit is still not connecting, | + | If the unit is still not connecting, |
+ | |||
+ | Check the VE.Bus Monitor and AC Input Connection timer | ||
+ | |||
+ | {{:: | ||
+ | |||
+ | With Multi firmwares xxyy460 and up, VEConfig will indicate why the AC Input is rejected and will also show an indication of the remaining waiting time as a blue bar. | ||
+ | |||
+ | After the waiting time the unit will connect to AC input provided that there is no assistant which prevents the unit from connecting to grid and that the required relay test is performed. | ||
+ | |||
+ | Switch | ||
Try with a different generator. | Try with a different generator. | ||
- | There can be issues with generators with Residual Current Devices (RCD' | + | As troubleshooting and correcting these faults have serious safety implications, |
+ | There can be issues with generators with Residual Current Devices (RCD' | ||
+ | |||
+ | Simplify the AC wiring, With everything safely shut down and tested for voltage, disconnect the AC-Output active, neutral and earth. Direct wire in the generator connections, | ||
If there is still no connection, contact your dealer or distributor. Tell them the steps that you have taken already to attempt to get it to work and they can help from there. | If there is still no connection, contact your dealer or distributor. Tell them the steps that you have taken already to attempt to get it to work and they can help from there. | ||
Line 210: | Line 255: | ||
[[https:// | [[https:// | ||
+ | |||
+ | [[https:// | ||
[[https:// | [[https:// | ||
Line 219: | Line 266: | ||
[[https:// | [[https:// | ||
+ | [[https:// | ||
+ | |||
+ | ===== Community Discussion on MultiPlus 2x120 and generator phase compatibility ===== | ||
+ | |||
+ | [[https:// | ||
+ | [[https:// | ||
- | ===== DISQUS ===== | ||
- | ~~DISQUS~~ |
multiplus_faq.1571312924.txt.gz · Last modified: 2019-10-17 13:48 by guystewart