In 2019 SolarEdge has introduced a new feature that allows AC-coupling with alternative power sources (or non-grid power sources) such as the Victron Energy Inverter/ | In 2019 SolarEdge has introduced a new feature that allows AC-coupling with alternative power sources (or non-grid power sources) such as the Victron Energy Inverter/ | ||
- | When a solar inverter is operating concurrently with a non-grid source, it may be subjected to voltage and frequency fluctuations that exceed | + | When a solar inverter is operating concurrently with a non-grid source, it may be subjected to voltage and frequency fluctuations that exceed |
- | With this feature you can now build custom size AC Coupled Hybrid systems with the capability to enable zero feed-in to the grid when in On-Grid mode and frequency shifting power control in Off-Grid situations | + | With this feature you can now build custom size AC Coupled Hybrid |
+ | |||
+ | For more information: | ||
The AC coupled system sizing guideline, Factor 1.0 rule, from Victron Energy for AC coupled system must be adhered to. | The AC coupled system sizing guideline, Factor 1.0 rule, from Victron Energy for AC coupled system must be adhered to. | ||
+ | |||
+ | **Note** | ||
+ | |||
+ | This APS feature is only available for 3phase and 1phase HDwave inverters. | ||
===== 2. How to configure APS mode ===== | ===== 2. How to configure APS mode ===== | ||
Line 14: | Line 20: | ||
Requirements: | Requirements: | ||
- | * For SetApp (screenless) inverters: Firmware 4.8.24 or higher | + | * For SetApp (screenless) inverters: Firmware 4.8.24 or higher |
* For LCD inverters: Firmware 3.25xx or higher | * For LCD inverters: Firmware 3.25xx or higher | ||
Line 22: | Line 28: | ||
* SolarEdge grid meter (required for Zero feedback) | * SolarEdge grid meter (required for Zero feedback) | ||
- | Note: APS mode is mandatory for systems requiring both zero feed-in in on-grid mode and frequency shifting in off-grid mode. | ||
- | Configuration example 1: Use of external relay and dry contact, see figure 1 | + | Configuration example 1: Use of external relay and dry contact, Single-phase configuration, see figure 1 |
Line 36: | Line 41: | ||
;#; | ;#; | ||
- | ;#; | ||
+ | Three Phase configuration, | ||
- | |||
- | |||
- | |||
- | #;; | ||
- | Configuration example 2: Use of Internal programmable relay K1, See Figure 2 | ||
- | #;; | ||
;#; | ;#; | ||
- | ;#; | + | {{: |
- | {{: | + | |
;#; | ;#; | ||
- | ;#; | ||
- | |||
- | ;#; | ||
;#; | ;#; | ||
Figure 2 | Figure 2 | ||
Line 60: | Line 55: | ||
- | Programmable | + | Configuration example 2: Use of Internal programmable |
+ | |||
+ | Single-phase configuration, | ||
;#; | ;#; | ||
- | ;#; | + | {{: |
- | ;#; | + | |
- | {{: | + | |
;#; | ;#; | ||
- | ;#; | ||
+ | ;#; | ||
+ | Figure 3 | ||
;#; | ;#; | ||
- | + | Three-phase configuration, See Figure | |
- | + | ||
- | + | ||
- | __1. Dry contact installation__ | + | |
- | + | ||
- | Install a dry contact, sensing the grid availability. Connect twisted pair wires from the dry contact terminals to the L1 and V terminals of the Communication Board inside the inverter, see figure | + | |
- | + | ||
;#; | ;#; | ||
- | {{: | + | {{: |
;#; | ;#; | ||
Line 88: | Line 79: | ||
;#; | ;#; | ||
+ | Programmable Aux relay Set up, single-phase configuration, | ||
- | __2. Alternative Power Source mode__ | ||
- | |||
- | Alternative Power Source mode should be configured on the master inverter. Once configured, the master inverter automatically sets all detected slave inverters to Alternative Power Source mode. | ||
- | |||
- | To Configure Alternative Power Source mode: | ||
- | |||
- | * Commissioning -> Communication -> GPIO -> Power Reduction Interface (RRCR) Mode -> Alternative Power Source. | ||
;#; | ;#; | ||
- | {{: | + | {{: |
;#; | ;#; | ||
- | |||
- | |||
- | |||
- | |||
- | Inverters with LCD | ||
- | |||
- | * Enter the inverter’s setup menu using the SolarEdge Password. | ||
- | |||
- | * Communication -> GPIO Conf -> Device Type -> Alternative Power Src. | ||
;#; | ;#; | ||
- | {{: | + | Figure 5 |
;#; | ;#; | ||
- | + | Programmable Aux relay Set up, three-phase configuration, | |
- | + | ||
- | + | ||
- | + | ||
- | + | ||
- | + | ||
- | + | ||
- | ===== 3. How to configure Frequency Shifting ===== | + | |
- | + | ||
- | + | ||
- | Important note: Please ensure the SolarEdge inverter and your VE.Bus Config is set up for the same frequency bandwidth. | + | |
- | + | ||
- | **For systems that can feedback into the grid or for pure off-grid systems**: | + | |
- | + | ||
- | __1. Enable frequency shifting__ | + | |
- | + | ||
- | * Go into Power Control | + | |
- | + | ||
- | * Ensure Grid control is Enabled | + | |
;#; | ;#; | ||
- | {{: | + | {{: |
;#; | ;#; | ||
- | |||
- | | ||
;#; | ;#; | ||
- | {{: | + | Figure 6 |
;#; | ;#; | ||
- | __2. Configure Wakeup Conf.__ | ||
- | * Power Control -> Wakeup Profile -> Edit | ||
- | * Edit Maximum Wake up Frequency = 51.2Hz | ||
- | ;#; | + | __1. Dry contact installation__ |
- | {{: | + | |
- | ;#; | + | |
- | + | ||
- | + | ||
- | Inverters with LCD: | + | |
- | * Power Control -> Wakeup Profile -> Edit | + | |
+ | Install a dry contact, sensing the grid availability. Connect twisted pair wires from the dry contact terminals to the L1 and V terminals of the Communication Board inside the inverter, see figure 4. | ||
+ | |||
;#; | ;#; | ||
- | {{: | + | {{: |
;#; | ;#; | ||
- | |||
- | |||
- | __3. Disable Wakeup gradient__ | ||
- | |||
- | * Power Control -> Active Power control -> Wakeup Gradient -> Disable | ||
;#; | ;#; | ||
- | {{: | + | Figure 4 |
;#; | ;#; | ||
- | |||
- | + | __2. Alternative Power Source mode__ | |
- | Inverters with LCD | + | |
- | * Power Control -> Active | + | Alternative |
- | ;#; | + | To Configure Alternative Power Source mode: |
- | {{:venus-os: | + | |
- | ;#; | + | |
- | + | | |
- | + | ||
- | __4. Set P(F)__ | + | |
- | + | ||
- | | + | |
- | + | ||
- | * Edit P0: 50.5Hz, 100% Power | + | |
- | + | ||
- | * and P1: 51.2Hz, 0% Power | + | |
;#; | ;#; | ||
- | | + | |
;#; | ;#; | ||
+ | |||
+ | |||
Inverters with LCD | Inverters with LCD | ||
- | * Power Control -> Active Power control -> P(f) | + | * Enter the inverter’s setup menu using the SolarEdge Password. |
- | * Edit P0: 50.5Hz, 100% Power | + | * Communication -> GPIO Conf -> Device Type -> Alternative |
- | + | ||
- | * and P1: 51.2Hz, 0% Power | + | |
;#; | ;#; | ||
- | {{: | + | {{: |
;#; | ;#; | ||
Line 222: | Line 154: | ||
+ | ===== 3. How to configure Frequency Shifting ===== | ||
- | + | Important note: Please ensure | |
- | **For systems with zero grid feed-in** | + | |
- | + | ||
- | In addition to the frequency settings above, please | + | |
__1. Configure P(f) for APS__ | __1. Configure P(f) for APS__ | ||
Line 233: | Line 163: | ||
* Power Control -> Alternative Power Source -> P(f) | * Power Control -> Alternative Power Source -> P(f) | ||
- | * Edit P0: 50.5Hz, 100% Power | + | * Edit P0: 50.2Hz, 100% Power |
* and P1: 51.2Hz, 0% Power | * and P1: 51.2Hz, 0% Power | ||
Line 247: | Line 177: | ||
* Power Control -> Alt Power Src-> P(f) | * Power Control -> Alt Power Src-> P(f) | ||
- | * Edit P0: 50.5Hz, 100% Power | + | * Edit P0: 50.2Hz, 100% Power |
* and P1: 51.2Hz, 0% Power | * and P1: 51.2Hz, 0% Power | ||
Line 255: | Line 185: | ||
;#; | ;#; | ||
+ | **__Note:__ | ||
- | + | In addition to the settings above it is important to contact SolarEdge Support to change a parameter in the backend to allow the frequency shifting with APS mode.** | |
Line 350: | Line 280: | ||
**Note: | **Note: | ||
It also advised editing the SolarEdge inverter’s IP address to a static IP by disabling DHCP edit the desired IP address for your SolarEdge inverter and the search for the IP address on your DX Device. The SolarEdge inverter will appear on you GX devices screen | It also advised editing the SolarEdge inverter’s IP address to a static IP by disabling DHCP edit the desired IP address for your SolarEdge inverter and the search for the IP address on your DX Device. The SolarEdge inverter will appear on you GX devices screen | ||
+ | |||
+ | |||
+ | ===== 6 For multiple SolarEdge inverter integration ===== | ||
+ | |||
+ | - The SolarEdge inverter needs to be interconnected via RS485-1, with a Leader, follower configuration. | ||
+ | - Only the Leader SolarEdge inverter requires the dry-relay contact connection. (section 1) | ||
+ | - Only the Leader SolarEdge inverter requires the GPIO setting to Alternative Power Source configuration. (section 2) | ||
+ | - Enable Grid Control for all the SolarEdge inverters on site. (Power control -> Grid Control -> Enable) | ||
+ | - Setup the frequency shifting bandwidth for all the SolarEdge inverters on site. (section 3) | ||
+ | - Each inverter requires its own TCP connection and IP address with the same SunSpec setting for each inverter. (Section 5) | ||