Blue Smart IP22 Charger

Commencing a new charge cycle

A new charge cycle will commence when:

  1. The configured Re-bulk condition is satisfied (typically due to a large load):

    1. Re-bulk method set to Current and Re-bulk current is disabled (default configuration): The current output must be maintained at the maximum current output for four seconds.

    2. Re-bulk method is set to Current and Re-bulk current is configured with a user defined value: The current output must exceed the configured Re-bulk current for four seconds while the charger is in float or storage stage.

    3. Re-bulk method is set to Voltage and Re-bulk voltage offset is configured with a user defined value: The battery voltage must drop below the configured Re-bulk voltage for one minute.

    4. The charger is in a VE.Smart network with synchronised charging: The battery voltage must drop below the configured Re-bulk voltage for one minute (regardless of the Re-bulk method selected).

  2. The MODE button is pressed or used to select a new charge mode.

  3. VictronConnect is used to select a new charge mode or change the function from Power Supply to Charger mode.

  4. The power supply to the AC power supply has been disconnected and reconnected.